300/500V XLPE Insulated, PVC Sheathed Power Cables (Single Core)

Application:

The cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings.

STANDARDS:

Basic design to IEC 60502-1

FIRE PERFORMANCE

Flame Retardance (Single Vertical Wire Test)**

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE 0482-332-1 ; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

Reduced Fire Propagation (Vertically-mounted bundled wires & cable test)**

EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24; VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Note: Asterisk ** denotes that the standard compliance is optional, depending on the oxygen index of the PVC compound and the cable design.

VOLTAGE RATING

300/500V

CABLE CONSTRUCTION

Conductor: Plain annealed copper wire, stranded according to IEC(EN) 60228 class 2.

Insulation: Extruded cross-linked XLPE compound.

Outer Sheath: Thermoplastic PVC compound. UV resistance, hydrocarbon resistance, oil resistance, anti rodent and anti termite properties can be offered as option. Compliance to fire performance standard (IEC 60332-1, IEC 60332-3, UL 1581, UL 1666 etc) depends on the oxygen index of the PVC compound and the overall cable design. LSPVC can also be provided upon request.

COLOUR CODE

Insulation Colour as per BS7671


With Earth Conductor

Without Earth Conductor

2Cores

-

Brown, Blue

3Cores

Yellow/Green, Brown, Blue

Brown, Gray, Black

4Cores

Yellow/Green, Brown, Gray, Black

Brown, Gray, Black, Blue

5Cores

Yellow/Green, Brown, Gray, Black, Blue

Brown, Gray, Black, Blue, Black

Above 5 Cores

Yellow/Green, Black Numbered

Black Numbered

Sheath Colour: Black (other colors upon request)

Physical AND THERMAL PROPERTIES

Temperature range during operation: Max.90°C for XLPE

250°C in short-circuit for 5secs max.

Minimum bending radius: 6 x Overall Diameter (unarmoured cable)

10 x Overall Diameter (armoured cable)

CONSTRUCTION PARAMETERS

Conductor


No. of Core X Cross Section

No./Nominal Diameter of Strands

Nominal Insulation Thickness

Nominal Overall Diameter

Nominal Overall Diameter

Noxmm2

No./mm

mm

mm

kg/km

1x1.5

7/0.53

0.50

3.8

27

1x2.5

7/0.67

0.50

4.2

37

1x4.0

7/0.85

0.50

4.8

54

Electrical Properties

Conductor Operating Temperature : 90°C

Ambient Temperature : 30°C

Current-Carrying Capacities (Amp)

Conductor crosssectional area

Reference Method 4 (enclosed in conduit in thermally insulating wall etc)

Reference Method 3 (enclosed in conduit on a wall or in trunking etc)

Reference Method 1 (clipped direct)

Reference Method 11 (on a perforated cable tray, horizontal or vertical)

Reference Method 12 (free air)

Horizontal flat spaced

Vertical flat spaced

Trefoil


2 cables, single- phase a.c. or d.c.

3 or 4 cables, 3-phase a.c.

2 cables, single- phase a.c. or d.c

3 or 4 cables, 3-phase a.c.

2 cables, single- phase a.c. or d.c. flat and touching

3 or 4 cables, 3-phase a.c. flat and touching or trefoil

2 cables, single- phase a.c. or d.c. or flat and touching

3 or 4 cables, 3-phase a.c. flat and touching or trefoil

2 cables, single- phase a.c. or d.c. or 3 c ables three phase

2 cables, single- phase a.c. or d.c. or 3 cables three phase

3 cables, trefoil 3-phase a.c.

1

2

3

4

5

6

7

8

9

10

11

12

mm2

A

A

A

A

A

A

A

A

A

A

A

1.5

18

17

22

19

25

23

-

-

-

-

-

2.5

24

23

30

26

34

31

-

-

-

-

-

4

33

30

40

35

46

41

-

-

-

-

-

Voltage Drop (Per Amp Per Meter)

Nominal Cross Section Area

2 cables d.c.

2 cables, single-phase a.c.

3 or 4 cables, 3-phase a.c.

Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall)

Ref. Methods 1 and 11 (clipped direct or on trays touching)

Ref. Methods 3 and 4 (enclosed in conduit etc, in or on a wall)

Ref. Methods 1, 11 and 12 (in trefoil)

Ref. Methods 1 and 11(Flat and touching)

1

2

3

4

5

6

7

mm2

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

mV/A/m

1.5

31

31

27

27

27

27

2.5

19

19

16

16

16

16

4

33

12

10

10

10

10